Question 530
A risk assessor working with Silverpine Refining records this evidence: An inexpensive remote terminal unit is excluded from high-criticality review despite controlling a sole wastewater discharge valve. What specific root cause should the team identify?
Explanation
Correct Answer
In the assessment at Silverpine Refining, the decisive observed condition is: An inexpensive remote terminal unit is excluded from high-criticality review despite controlling a sole wastewater discharge valve. The responsible mechanism is: Asset criticality was inferred from replacement cost rather than process impact and safety consequences. An appropriately focused correction is: Recalculate criticality using operational dependencies, outage consequences and relevant safety scenarios. The checkable acceptance evidence is: The reassessed asset has a documented consequence-based classification approved by operations. This diagnosis response addresses the stated industrial-system assessment issue rather than an unrelated weakness.
Incorrect Answers
This diagnosis response addresses another preparing for an assessment situation: An integrator's startup laptop subnet has persistent reachability to production PLCs yet does not appear in the completed assessment boundary. That situation has the distinct causal mechanism: The assessment excludes a temporary segment without confirming its operational isolation or retirement. The present case instead turns on: Asset criticality was inferred from replacement cost rather than process impact and safety consequences.
This diagnosis response addresses another preparing for an assessment situation: A water-treatment IACS boundary diagram stops at the SCADA firewall although a remote-maintenance concentrator can initiate sessions to process controllers. That situation has the distinct causal mechanism: The system under consideration was drawn around production controllers without its externally reachable support access path. The present case instead turns on: Asset criticality was inferred from replacement cost rather than process impact and safety consequences.
This diagnosis response addresses another preparing for an assessment situation: A redundant control-room path is used during planned failover but disappears from the diagrams delivered to risk assessors. That situation has the distinct causal mechanism: The architecture inventory models the primary path only and omits a secondary network route relevant to exposure. The present case instead turns on: Asset criticality was inferred from replacement cost rather than process impact and safety consequences.



IC33 ISA-IEC 62443 Cybersecurity Risk Assessment Specialist Practice Tests